The program controller RD3 permits programming of temperature cycles. For each program section also
the fan speed can be regulated.
Two programs with up to 10 sections each or one program with up to 20 sections can be entered (setting
in the user level, chap. 10).
When changing from 2 programs to 1 program or vice-versa, existing programs are deleted
The maximum length of an individual program section can be set to either 99 hs 59 min or to 999 hs 59
min (setting in the user level, chap. 10). This setting is then valid for all program sections.
Programming can be done directly via the controller keyboard or graphically at the computer using the
communication software APT-COM 3 DataControlSystem (option, chap. 16.1) specially developed by
BINDER.
5.2 General indications
The program controller RD3 offers several functional levels:
Normal Display / fixed value operation:
Display of the actual value of temperature (display 1) and of the actual date and time (display 2).
The chamber is in fixed value operating mode, equilibrating to the entered set-points.
Fixed value entry mode (chap. 6)
Entry of set-points for temperature, fan speed, and the safety controller for fixed value operating mode
Entry of temperature set-points SP 1 and SP 2 for week program operation
Program editor (chap. 8)
Two programs with up to 10 sections each or one program with up to 20 sections can be entered
(selection in the user level, chap. 10). Entry of set-points for temperature and fan speed in all program
sections (chap. 8.2).
Deleting a program section (chap. 8.4)
Program start level (chap. 9)
Selection of an entered program
Entry of settings affecting the program course, as start delay timeor number of program cycles
Program start
Week program editor (chap.7)
Setting the shift points
User level (chap. 10)
User specific controller settings
Setting the real time clock